Power · Rack Power
The density problem
Why 800V
Higher power per rack
Shelf ratings up to 110 kW, with distribution up to 400 kW.
Fewer conversion losses
DC-DC conversion at up to 98% peak efficiency.
Compact footprint
1RU and 3RU form factors keep power equipment out of the way of compute.
Built-in ride-through
Battery backup shelves carry critical loads through short outages and transients.
Applications
Product lineup
Power distribution
800V PDU
Distributes 800V DC power across the rack, splitting one high-current feed into four fused outputs.
Output power
400 kW
Input
1 × 500 A DC
Output
4 × 125 A DC
Protection
4 DC fuse boxes
Form factor
3RU
Dimensions
827 × 438 × 132.5 mm
Operating temp.
−5 to 45 °C
Request a PDU quote
AC-DC for 54V racks
110 kW Power Shelf
Converts three-phase AC into 54V DC for today’s 54V AI racks, with six 18.3 kW power supply modules in one shelf. A practical bridge while your site moves to 800V.
Output power
110 kW
Input
346–480 Vac L-L, 3L + PE, 2 × AC feeds
Output
54 V / 2,040 A
Communication
PMBus
Form factor
3RU
Dimensions
880 × 438 × 131.4 mm
Operating temp.
−5 to 45 °C
Request a Power Shelf quote
DC-DC conversion
800V DC-DC Shelf
Steps 800V DC down to 54V DC at the rack, at up to 98% peak efficiency.
Output power
90 kW
Input
800 VDC
Output
54 VDC
Peak efficiency
Up to 98%
Communication
PMBus (100 / 400 kHz)
Form factor
1RU
Dimensions
43.6 × 438 × 830 mm
Operating temp.
−5 to 45 °C
Request an 800V DC-DC Shelf quote
Battery backup
110 kW BBU Shelf
Keeps critical loads running through power interruptions and transients, with five 22 kW battery modules on the 800V bus.
Output power
110 kW
Input
800 V / 250 A
Output
800 V / 250 A
Communication
Modbus / CAN
Form factor
3RU
Dimensions
880 × 438 × 131.4 mm
Operating temp.
0 to 40 °C
Request a BBU Shelf quote
Specifications shown are nominal. Contact us for full datasheets, lead times, and configuration options.
Certifications and compliance
Power supply
UL / IEC 62368-1
Safety of AC-DC power shelves and power electronics
Conversion
IEC 62477-1
Safety of high-voltage DC power conversion equipment
Battery
UL 1973
Stationary batteries for backup power
Battery
UN 38.3
Safe transport of lithium-ion battery modules
Electronics
FCC Part 15 Class A
Electromagnetic compatibility
Certifications vary by product and configuration. Certificates and listing numbers are available on request.
Your single point of contact
Managed by ASpeed AI Power
Specification and quote
Equipment and delivery
Installation and commissioning
Maintenance and support
How it works
01
Share requirements
Your rack densities, input power, backup runtime, and timeline.
02
Get recommendations
Rack power configurations with pricing and lead times.
03
Delivery and startup
Delivery, installation, and commissioning through our service network.
04
Stay connected
Your ASpeed AI Power contact stays with the project through handoff.
Planning cooling for the same racks?
Pair 800V rack power with liquid cooling sized for the same densities.